The Control of Pollution (Oil Storage) (England) Regulations 2001 © Crown Copyright 2001 The legislation contained on this web site is subject to Crown Copyright protection. It may be reproduced free of charge provided that it is reproduced accurately and that the source and copyright status of the material is made evident to users. It should be noted that the right to reproduce the text of Statutory Instruments does not extend to the Royal Arms and the Queen's Printer imprints. The text of this Internet version of the Statutory Instrument has been prepared to reflect the text as it was Made. The authoritative version is the Queen's Printer copy published by The Stationery Office Limited as the The Control of Pollution (Oil Storage) (England) Regulations 2001, ISBN 0 11 029895 0. Purchase this item. For details of how to obtain an official copy see How to obtain The Stationery Office Limited titles. To ensure fast access over slow connections, large documents have been segmented into "chunks". Where you see a "continue" button at the bottom of the page of text, this indicates that there is another chunk of text available.
The Secretary of State, in exercise of the powers conferred upon her by sections 92 and 219(2) of the Water Resources Act 1991[1], hereby makes the following Regulations: Citation, commencement, extent and interpretation 1. - (1) These Regulations, which may be cited as the Control of Pollution (Oil Storage) (England) Regulations 2001, shall come into force on 1st March 2002 and extend to England only. (2) In these Regulations -
Application of Regulations
(b) in any container which is situated in a building or wholly underground; (c) in any container with a storage capacity of 200 litres or less; (d) on any premises used -
(ii) for refining oil; or (iii) for the onward distribution of oil to other places; or
(e) on any farm if the oil is for use in connection with agriculture within the meaning of the Agriculture Act 1947[3].
Requirements for storage of oil - general
(b) it must be positioned, or other steps must be taken, so as to minimise any risk of damage by impact so far as is reasonably practicable; (c) its base and walls must be impermeable to water and oil; (d) its base and walls must not be penetrated by any valve, pipe or other opening which is used for draining the system; and (e) if any fill pipe, or draw off pipe, penetrates its base or any of its walls, the junction of the pipe with the base or walls must be adequately sealed to prevent oil escaping from the system.
(3) Any valve, filter, sight gauge, vent pipe or other equipment ancillary to the container (other than a fill pipe or draw off pipe or, if the oil has a flashpoint of less than 32°C, a pump) must be situated within the secondary containment system.
(b) if there is more than one drum used at the same time with the tray, the aggregate storage capacity of the drums.
Fixed tanks
(b) if underground -
(ii) must be adequately protected from physical damage; (iii) must have adequate facilities for detecting any leaks; (iv) if fitted with a leakage detection device which is used continuously to monitor for leaks, the detection device must be maintained in working order and tested at appropriate intervals to ensure that it works properly; and (v) if not fitted with such a device, must be tested for leaks before it is first used and further tests for leaks must be performed, in the case of pipes which have mechanical joints, at least once in every 5 years and, in other cases, at least once in every 10 years; and
(c) if made of materials which are liable to corrosion, must be adequately protected against corrosion.
(4) The tank must be fitted with an automatic overfill prevention device if the filling operation is controlled from a place where it is not reasonably practicable to observe the tank and any vent pipe.
(b) the tap or valve must not be capable of being fixed in the open position unless the pipe is fitted with an automatic shut off device; (c) the pipe must be enclosed in a secure cabinet which is locked shut when not in use and is equipped with a drip tray or the pipe must -
(ii) be kept within the secondary containment system when not in use.
(7) Any pump must be -
(b) positioned, or other steps must be taken, so as to minimise any risk of damage by impact so far as is reasonably practicable; and (c) protected from unauthorised use.
(8) Any permanent vent pipe, tap or valve through which oil can be discharged from the tank to the open must satisfy the following requirements -
(b) it must be arranged so as to discharge the oil vertically downwards and be contained within the system; and (c) in the case of a tap or valve, it must be fitted with a lock and locked shut when not in use.
Mobile bowsers
(b) the pump or valve must be provided with a lock and locked shut when not in use; (c) the pipe must be fitted with a lockable valve at the end where it leaves the container and must be locked shut when not in use.
Transitional provisions
(b) 50 metres away from a well or borehole.
the preceding provisions of these Regulations shall apply from 1st September 2003.
(b) if the period for compliance is extended under regulation 7(4), the expiry of the extension; (c) if there is an appeal against the notice, the date on which the appeal is determined or withdrawn.
Notices to minimise pollution risks in transitional cases
(b) the Agency considers that there is a significant risk of pollution of controlled waters from the entry of the oil in question into those waters if steps are not immediately taken to minimise that risk,
the Agency may serve notice on the person having custody or control of that oil requiring him to carry out such works, take such precautions or such other steps as, in the opinion of the Agency, are appropriate for minimising that risk having regard to the requirements of regulations 3 to 5.
(b) state the period within which any such requirement is to be complied with; and (c) inform him of his rights under regulation 8.
(3) The period for compliance shall be such period as is reasonable in the circumstances and shall not in any case be less than 28 days.
(b) extend the period for compliance with any requirement of the notice; (c) with the consent of the person on whom it is served, modify the requirements of the notice,
and shall do so if so directed by the Secretary of State under regulation 8(4).
(b) if requested to do so by the appellant or the Agency, afford them the opportunity of appearing before and being heard by a person appointed by the Secretary of State for the purpose.
(4) On determining an appeal the Secretary of State may direct the Agency to withdraw the notice under regulation 7, modify any of its requirements, extend the period for compliance or dismiss the appeal.
(b) on conviction on indictment, to a fine.
(This note is not part of the Regulations) These Regulations require a person having custody or control of oil to carry out certain works and take certain precautions and other steps for preventing pollution of any waters which are controlled waters for the purposes of Part III of the Water Resources Act 1991. Regulation 2(2) sets out circumstances in which these Regulations do not apply to the storage of oil. Regulation 3 imposes general requirements in relation to the storage of oil. Additional requirements which apply to specific types of container are imposed by regulation 4 (fixed tanks) and regulation 5 (mobile bowsers). Regulation 6 contains transitional provisions. Where in a transitional case the Environment Agency considers that there is a significant risk of pollution of controlled waters from the oil in question it has the power to serve a notice on the person having custody or control to minimise the risk (see regulation 7). A person served with a notice has a right of appeal to the Secretary of State under regulation 8. Failure to comply with any of the requirements of regulations 3 to 5 or a notice under regulation 7 is a criminal offence (see regulation 9), punishable on conviction on indictment to an unlimited fine or on summary conviction to a fine not exceeding the statutory maximum (currently £5,000). Notes: [1] 1991 c. 57; there are amendments to sections 92 and 219(2) which are not relevant to these regulations. The relevant powers of the Secretary of State have been devolved in relation to Wales by article 2 of the National Assembly for Wales (Transfer of Functions) Order 1999 (S.I. 1999/672), although there are concurrent powers in relation to those parts of Wales which are within the catchment areas of the rivers, Dee, Wye and Severn (see the entry in Schedule 1 to the Order for the Water Resources Act 1991).back [2] S.I. 1994/1056; to which there are amendments not relevant to these regulations.back
ISBN 0 11 029895 0
|
| ||
We welcome your comments on this site | © Crown copyright 2001 | Prepared 29 August 2001 |